Vui lòng dùng định danh này để trích dẫn hoặc liên kết đến tài liệu này:
https://dspace.ctu.edu.vn/jspui/handle/123456789/21868
Nhan đề: | Ozonation process and water disintection |
Tác giả: | Nguyen, Hoang Nghi Le, Cao Cuong Tran, Vinh Dieu Tu Ngu Doan, Thi Yen Oanh |
Từ khoá: | Ozone Oxidant Disinfectant ORP (oxidation-reduce potential) Time-dependent ORP Total coliform |
Năm xuất bản: | 2018 |
Tùng thư/Số báo cáo: | Vietnam Journal of Chemistry;No 56(06) .- Page.717-720 |
Tóm tắt: | As commonly known, ozone is a highly effective disinfectant for both aqueous and gaseous media. It works through oxidation. Dissolved ozone causes the increases of the redox potential ORP of water. During the ozonenation process, the time-dependent redox potential ORP of water depends strongly on the density of microbes in it. By analyzing the time-dependent redox potential, it is possible to measure and calculate the parameters such as the oxidizing rate, the maximal redox potential ORPmax etc. of the ozonated water. These parameters of water reflect the microbiological pollution level of water. Ozonated water having a certain ORP level obtains disinfecting ability. Bacteriological analysis of the water samples after ozonation show that total coliform and E. coli bacteria were fully removed after a few minutes at ORP of 800 mV. |