Vui lòng dùng định danh này để trích dẫn hoặc liên kết đến tài liệu này: https://dspace.ctu.edu.vn/jspui/handle/123456789/38521
Nhan đề: Control of a permanent-magnet synchronous generator wind turbine system during grid fault
Tác giả: Van, Tan Luong
Dang, Ngoc Khoa
Từ khoá: Braking chopper
Permanent-magnet synchronous generator
Unbalanced voltage
Wind turbine
Năm xuất bản: 2019
Tùng thư/Số báo cáo: Journal of Science Technology and Food;Vol. 19, No. 02 .- P.2-12
Tóm tắt: In this research, an enhanced control scheme for the permanent-magnet synchronous generator (PMSG) wind turbines under grid voltage fault condition is introduced. The machine-side converter (MSC) Controls the DC-link voltage; however, this voltage value can bc still increased during the grid fault. Thus, the braking chopper (BC) added to the DC-bus will be activated to dissipate the surplur power between the grid and generator powers. Meanwhile, the grid active power is regulated at the grid-side converter (GSC), from which can be exploited to inject reactive current into the grid tor assisting thc grid voltage recovery. Also, an algorithm of positive-sequence current control in the dq-axis is implemented, based on feedback linearization theory. The validity of this control algorithm has been verified bv the simulation of the 2MW-PMSG wind turbine System.
Định danh: https://dspace.ctu.edu.vn/jspui/handle/123456789/38521
ISSN: 0866-8132
Bộ sưu tập: Khoa học Công nghệ và Thực phẩm

Các tập tin trong tài liệu này:
Tập tin Mô tả Kích thước Định dạng  
_file_
  Giới hạn truy cập
2.27 MBAdobe PDF
Your IP: 18.222.107.27


Khi sử dụng các tài liệu trong Thư viện số phải tuân thủ Luật bản quyền.