Vui lòng dùng định danh này để trích dẫn hoặc liên kết đến tài liệu này:
https://dspace.ctu.edu.vn/jspui/handle/123456789/38521
Nhan đề: | Control of a permanent-magnet synchronous generator wind turbine system during grid fault |
Tác giả: | Van, Tan Luong Dang, Ngoc Khoa |
Từ khoá: | Braking chopper Permanent-magnet synchronous generator Unbalanced voltage Wind turbine |
Năm xuất bản: | 2019 |
Tùng thư/Số báo cáo: | Journal of Science Technology and Food;Vol. 19, No. 02 .- P.2-12 |
Tóm tắt: | In this research, an enhanced control scheme for the permanent-magnet synchronous generator (PMSG) wind turbines under grid voltage fault condition is introduced. The machine-side converter (MSC) Controls the DC-link voltage; however, this voltage value can bc still increased during the grid fault. Thus, the braking chopper (BC) added to the DC-bus will be activated to dissipate the surplur power between the grid and generator powers. Meanwhile, the grid active power is regulated at the grid-side converter (GSC), from which can be exploited to inject reactive current into the grid tor assisting thc grid voltage recovery. Also, an algorithm of positive-sequence current control in the dq-axis is implemented, based on feedback linearization theory. The validity of this control algorithm has been verified bv the simulation of the 2MW-PMSG wind turbine System. |
Định danh: | https://dspace.ctu.edu.vn/jspui/handle/123456789/38521 |
ISSN: | 0866-8132 |
Bộ sưu tập: | Khoa học Công nghệ và Thực phẩm |
Các tập tin trong tài liệu này:
Tập tin | Mô tả | Kích thước | Định dạng | |
---|---|---|---|---|
_file_ Giới hạn truy cập | 2.27 MB | Adobe PDF | ||
Your IP: 18.222.107.27 |
Khi sử dụng các tài liệu trong Thư viện số phải tuân thủ Luật bản quyền.