dc.description.abstract | This paper proposes a nonlinear control of dynamic voltage restorer (DVR) based on a feedback linearization (FL) theory to improve a Iow-voltage ride-through (LVRT) capability of a doubly fed induction generator (DFIG) wind turbine System. First, the nonlinear model of the System including LC filter is obtained in the d-q synchronous reference frame. Then, the controller design of the linearized model is performed by the multi-input multi-output feedback linearization. The simulation results for the 2 MW-DFIG wind turbine System with the DVR compensation at grid faults gives as good performance as those without grid faults. | vi_VN |
dc.language.iso | en | vi_VN |
dc.relation.ispartofseries | Journal of Science Technology and Food;Vol. 19, No. 02 .- P.13-22 | - |
dc.subject | Doubly-ted induction generator | vi_VN |
dc.subject | Dynamic voltage restorer | vi_VN |
dc.subject | Feedback linearization theory | vi_VN |
dc.subject | Voltage sag | vi_VN |
dc.subject | Wind turbine | vi_VN |
dc.title | Nonlinear control of dynamic voltage restorer to improve lvrt capability in wind turbine systems | vi_VN |
dc.type | Article | vi_VN |
Appears in Collections: | Khoa học Công nghệ và Thực phẩm |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
_file_ Restricted Access | 2.13 MB | Adobe PDF | ||
Your IP: 3.146.178.220 |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.