Nhan đề: | Control of voltage compensation to enhance ride through of dftg wind turbine during symmetrical and asymmetrical grid faults |
Tác giả: | Nguyên, Thi Thanh Truc Van, Tan Luong Phan, Thi Chieu My |
Từ khoá: | Doubly-fed induction generator Low-voltage ride-through Series compensation Voltage sag Wind turbine |
Năm xuất bản: | 2020 |
Tùng thư/Số báo cáo: | Journal of Science Technology and Food;Vol. 20, No. 02 .- P.31-41 |
Tóm tắt: | In this paper, the application of a series grid-side converter (SEGSC) connected to a wind-turbine-driven doubly fed induction generator (DFIG) is introduced. The setup allows the wind turbine System an uninterruptible fault ride-through of voltage dips. The SEGSC can compensate the faulty line voltage, while the DFIG wind turbine can continue its nominal operation as demanded in actual grid codes. The simulation results for the 2 MW-DFIG wind turbine System with the SEGSC compensation are presented, especially for asymmetrical grid faults, gives as good performance as those without grid faults. |
Định danh: | https://dspace.ctu.edu.vn/jspui/handle/123456789/38554 |
ISSN: | 0866-8132 |